![]() I think you're wrong that the metallic raceway (conduit) isn't required to be bonded to the EGC: ![]() ![]() It *is* a requirement for a GEC to bond both ends (and probably I was conflating EGC and GEC rules ) (But I think if you have a metal jbox at each end that you will bond it that way anyhow.) You would be right to say that it isn't a requirement for an EGC to bond both ends of the conduit. The only conductor required to be bonded to the metallic raceway is the Ground Electrode Conductor, and there can only be 1 single GEC, and the GEC is ran from your AC Service Neutral to the Ground Electrode attachment point which has nothing to do with solar panels. "A bare wire (or any ground) should be bonded at both ends (usually via locknut->metal-j-box->groundscrew at each end of the conduit)" -meįalse statement.